HSE Report No. HSE-BPGRANGEMOUTH-HC-1987 1987 Fire Fire Explosion Explosion
BP Grangemouth 加氢裂化器低压分离器 V306 爆炸火灾(1987,无死亡)
BP Oil Grangemouth Refinery, Scotland, UK (HSE Sragtech Case)
Related equipment type → Pressure Vessel (Pressure Vessel)Related equipment → Control valve (control_valve)
0Fatalities
0Injuries
ExplosionMechanism code OTH
Failure Mode · ISO 14224 Mapping
Damage mechanism (recorded in KB)
ExplosionOTH
ISO functional code (as recorded)
ISO 14224:2016 functional failure code
OTH · Other
ISO OTH — Other.
1What Happened

HP 分离器液位低低跳闸多年前被解除;操作员不信任液位计、依赖带偏差的图表记录仪;HP 分离器液位低时手动反复开关液力控制阀,使高压气体窜入 LP 分离器 V306,LP 分离器安全阀按火灾工况而非气体突破工况设定→V306 超压爆炸

2Root Cause

LP 分离器安全阀未按气体突破工况设定;HP 分离器低低液位跳闸被解除;操作依赖带偏差图表记录仪;改造未做 HAZOP

3Reliability Lessons (from investigation root cause)
  • The 'Root Cause' above is the core lesson of this accident; not split further.
4Associated Failure Mechanisms (Keywords)
控制阀 液位 低低液位跳闸 解除联锁 气体突破 分离器 超压 泄放阀 加氢裂化
About the Failure-Mode Code (click to expand)

The recorded code OTH is an ISO 14224:2016 functional failure code (describes what the equipment failed to do). The damage mechanism (how it failed) is shown in the Mapping block above. The two are distinct dimensions in ISO 14224.

5Evidence Source (transparent)
Authority:Health and Safety Executive (HSE), UK — Sragtech Case Study
Official Report:www.hse.gov.uk ↗
Data Verification:verified_url_hse_2026-08-07
Related Failure Modes · Traceability

This accident is not yet linked to a specific FM traceability card.

Report No. HSE-BPGRANGEMOUTH-HC-1987 · Data from HSE public investigation conclusions, compiled by Reliability AI, for reliability demonstration purposes only. This case is derived from public incident investigation reports for learning purposes only. AIM does not endorse or guarantee its accuracy.