FM Traceability Card · trace the source basis (tap links to trace back)
← Back to KB navigation
Equipment B-201A FM fm_4 ISO 14224 mode OHE Overheating Source OPC Ontology KB
Grease Dry-out -> Overheating
B-201A · Fan / Blower
Related equipment → B-201A
0.75Source conf.
0.70Evidence conf.
OHEISO 14224 mode
1Failure Mechanism

Function:实现设备功能

Failure cause:润滑脂加注周期过长;轴承工作温度过高;润滑脂型号不适用

2Source Basis (where this FM comes from)
OPC Ontology KBCSB Accident DBQuant benchmark

Source confidence 0.75: this FM is derived from the ontology KB and cross-validated by OPC Ontology KB·CSB Accident DB·Quant benchmark.

3Evidence Chain (supporting basis)
Evidence text:None
Evidence conf.:0.7 · Evidence source:OEM_manual
4Related Real Accidents (traceable to accident cards)

This FM is recorded in 1 real accident investigation(s); tap the report no. to open the corresponding accident lesson card.

5Applicable Standards & Clauses
API 580GB/T 7826-2012ISO 14224:2016SAE JA1011_202411

Standard clause references (15):

GB/T 7826-2012GB/T 27921-2011GB/T 44958-2024GB/T 4888-2008GB/T 29639-2020AQ/T 3034-2022API 581API 580API 754API 689API 755ISO 14224:2016ISO 20815:2018IEC 61511:2016ISO 31000:2018
6Derived Analysis (seeded from this FM)
6/5/4FMEA Sev/Occ/Det
0.34RBI λ
0.8Monitor pdet
4 月Insp. int.

Current tasks:每运行2000小时加注润滑脂,每次加注量按轴承座容积的1/3 | 每日监测轴承温度,当温度超过70℃时检查润滑脂状态 | 每季度检查润滑脂颜色和稠度,发现变色或硬化时更换

RCFA incident:B-201A 发生润滑脂干涸→过热,严重程度 6,后果类型 Operational

7RCM Maintenance Decision (strategy landing)
CBMOn-Condition Maintenance
Recommended task温度/红外热成像监测, 超温报警与根因排查
Suggested intervalHigh risk 1-3 mo / Medium 6-12 mo / Low risk at turnaround (by API 581 RBI risk ranking)
Decision basis机理类别=overheat
Governing standards
API 530厂家规范
⚠ This decision is engineering-inferred by RCM logic from the damage mechanism / root cause / failure cause — it is not derived from measured site history. Confirm with the equipment owner and process before execution.
⚠ 本卡技术正文(功能 / 致因 / 损伤机理 / RCFA 叙事)保留中文原文——依可信 AI 红线,自由技术文本不自动机翻、不编造英文译文。UI、设备类型、FM 名、ISO 码、标准号均为英文。
FM fm_4 · Data from OPC KB and whitelisted public sources, compiled by Reliability AI for reliability demonstration only. Evidence ref codes are internal indices, not public DOIs.