Equipment FWP-101
FM fwp_suction_loss
ISO 14224 mode M M
Source engineering_estimate
吸水口堵塞/液位低
FWP-101 · Fire Water Pump
Related equipment → FWP-101
0.82Source conf.
—Evidence conf.
MISO 14224 mode
1Failure Mechanism
Function:保证进水
Failure cause:吸水池杂物/液位低致汽蚀或断流
Damage mechanism:吸水口堵塞致断流
2Source Basis (where this FM comes from)
engineering_estimate
Source confidence 0.82: this FM is derived from the ontology KB and cross-validated by engineering_estimate.
3Evidence Chain (supporting basis)
This FM has no offline curated evidence text; it is derived from the ontology KB and cross-validated by the listed standard clauses and related accident investigations.
Governing standards (evidence):std:NFPA 20 — Standard for the Installation of Stationary Pumps for Fire Protection · 机理级工程估计,非实测;引用 governing standard 作为分类出处
4Related Real Accidents (traceable to accident cards)
This FM is recorded in 3 real accident investigation(s); tap the report no. to open the corresponding accident lesson card.
5Applicable Standards & Clauses
NFPA 20
No separate clause reference.
6Derived Analysis (seeded from this FM)
8/2/5FMEA Sev/Occ/Det
0.03RBI λ
0.95Monitor pdet
6 月Insp. int.
Current tasks:吸水池清理 | 液位监测
RCFA incident:吸水口堵塞/液位低:吸水池杂物/液位低致汽蚀或断流,后果类型 Operational/Safety,严重度 8
7RCM Maintenance Decision (strategy landing)
CBMOn-Condition Maintenance
Recommended task入口压力/温度监测 + 叶轮表面蚀坑检查, 优化 NPSH 工况; 按压差/效率监测设定清洗周期 + 过滤/防堵维护
Suggested intervalHigh risk 1-3 mo / Medium 6-12 mo / Low risk at turnaround (by API 581 RBI risk ranking)
Decision basis机理类别=cavitation; fouling
Governing standardsAPI 571API 610API 617API 682厂家规范
⚠ This decision is engineering-inferred by RCM logic from the damage mechanism / root cause / failure cause — it is not derived from measured site history. Confirm with the equipment owner and process before execution.