← Back to KB navigation
Equipment FWP-101
FM fwp_controller_fail
ISO 14224 mode M M
Source engineering_estimate
控制盘/启动回路失效
FWP-101 · Fire Water Pump
Related equipment → FWP-101
0.82Source conf.
—Evidence conf.
MISO 14224 mode
1Failure Mechanism
Function:接收火警信号启动
Failure cause:控制盘继电器/启动回路故障致无法响应火警
Damage mechanism:控制回路故障致无响应
2Source Basis (where this FM comes from)
engineering_estimate
Source confidence 0.82: this FM is derived from the ontology KB and cross-validated by engineering_estimate.
3Evidence Chain (supporting basis)
This FM has no offline curated evidence text; it is derived from the ontology KB and cross-validated by the listed standard clauses and related accident investigations.
Governing standards (evidence):std:NFPA 20 — Standard for the Installation of Stationary Pumps for Fire Protection · 机理级工程估计,非实测;引用 governing standard 作为分类出处
4Related Real Accidents (traceable to accident cards)
This FM is recorded in 3 real accident investigation(s); tap the report no. to open the corresponding accident lesson card.
5Applicable Standards & Clauses
NFPA 20
No separate clause reference.
6Derived Analysis (seeded from this FM)
9/2/4FMEA Sev/Occ/Det
0.03RBI λ
0.95Monitor pdet
6 月Insp. int.
Current tasks:控制回路测试
RCFA incident:控制盘/启动回路失效:控制盘继电器/启动回路故障致无法响应火警,后果类型 Safety,严重度 9
7RCM Maintenance Decision (strategy landing)
PMScheduled (Proactive) Maintenance
Recommended task绝缘/电气试验 + 继电保护定值校核 + 操动机构特性测试; 标定/零点-跨度校验 + SIL Proof test + 阀门行程试验 + 变更管理
Suggested intervalHigh risk 1-3 mo / Medium 6-12 mo / Low risk at turnaround (by API 581 RBI risk ranking)
Decision basis机理类别=electrical; instrument
Governing standardsGB/T 14285GB/T 21109IEC 60034IEC 61511IEEE C57ISA 84
⚠ This decision is engineering-inferred by RCM logic from the damage mechanism / root cause / failure cause — it is not derived from measured site history. Confirm with the equipment owner and process before execution.